EDR-5000
IM02602007E
Device Planning Parameters of the Q->&V< Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
Do not use
[Device Planning]
Global Protection Parameters of the Q->&V< Module
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Q->&V<]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Q->&V<]
V Ext Release PCC Release Signal by the Point of Common Coupling. The
line-to-line voltage is greater than 95% of VN.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Q->&V<]
PCC Fuse Fail VT
Blocking if the fuse of a voltage transformer has tripped
at the PCC.
1..n, Dig Inputs
-.-
[Protection Para
/Global Prot Para
/Q->&V<]
Power Trip dir
By means of this parameter the trip direction of active
and reactive power can be inverted within the QV-Module
(sign reversal).
positive,
negative
positive
[Protection Para
/Global Prot Para
/Q->&V<]
Decoupling Functions of the Q->&V< Module
Name
Description
-.-
No assignment
50P[1].TripCmd
Signal: Trip Command
50P[2].TripCmd
Signal: Trip Command
50P[3].TripCmd
Signal: Trip Command
51P[1].TripCmd
Signal: Trip Command
51P[2].TripCmd
Signal: Trip Command
www.eaton.com
735