EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
V(t10)
Voltage value of a point V(t(n)). These points define the
LVRT profile.
0.00 - 1.30Vn
0.90Vn
[Protection Para
/<1..4>
/LVRT
/LVRT Profile]
t10
Point in time for the corresponding voltage value V(t(n)).
These points define the LVRT profile.
0.00 - 20.00s
3.00s
[Protection Para
/<1..4>
/LVRT
/LVRT Profile]
www.eaton.com