7.3 SWD device parameters
All device parameters can only be set via easySoft-Pro.
The device parameter “STOP on SWD error” enables you to define whether
easy800-SWD continues to process its circuit diagram in the event of an
error or switches to STOP mode. The POW LED also indicates the current
mode of easy800-SWD. A green flashing POW-LED indicates RUN mode, a
continuous green light indicates STOP mode. You can set the “STOP on
error” device parameter for easy800-SWD using the easySoft-Pro software.
A mandatory station is one with the “Mandatory station” device parameter
activated.
An “incorrect” station is one that easy800-SWD finds which, when
determining the actual configuration, is not expected in the target
configuration. Bear in mind that the serial number of the station is also
examined for matching as well as the station type. This means that if you
replace a pushbutton actuator with one of the same type when the SWD line
is switched off, it will be identified as an “incorrect” station by
easy800-SWD.
The “All devices are optional” and “Mandatory station” device parameters
determine whether an SWD error is present if the actual configuration is
different to the target configuration.
The “Compatible devices permissible” and “Replaceable with universal
module” device parameters determine whether an SWD error is present if
the target configuration is different to the project configuration.
The following table provides you with an overview:
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...