2 Installation
2.5 Connecting the inputs
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
35
Figure 29:AC expansion unit with EASY618-AC-RE with EASY256-HCI to increase the input
current
Connecting the DC inputs of the
800 standard
Use input terminals I1 to I12 of the DC easy800 standard to connect
pushbutton actuators, switches or 3- or 4-wire proximity switches. Given the
high residual current, do not use 2-wire proximity switches.
These DC easy800 standard enable you to read both digital and analog input
signals via the inputs I7 (IA01), I8 (IA02), I11 (IA03) and I12 (IA04).
•
Digital input signal voltage range
•
I1 to I6, I9, I10.
Signal OFF: 0 to 5 V.
Signal ON: 15 to 28.8 V.
•
I7, I8, I11, I12.
Signal OFF: < 8 V.
Signal ON: > 8 V.
•
Input current:
•
I1 to I6, I9, I10, R1 to R12: 3.3 mA at 24 V
•
I7, I8, I11, I12: 2.2 mA at 24°V
→
The increased capacitance increases the drop out delay by
approx. 40 ms.
→
Feed the digital inputs from the same 24 V DC power source as
the device.
L
N
R10
R9
R8
R7
R6
R5
R4
R3
R2
R1
E+ E–
R11 R12
N
N
L
115/230 V
h
F1
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...