5 Function blocks
5.9 CI, High-speed incremental value counter
174
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
5.9 CI, High-speed incremental value counter
All devices with DC inputs apart from EASY802-DC-SWD enable high-speed
up and down counting on a rising or falling edge. The counting operation is
independent of the cycle time.
You can set a lower and higher setpoint value as comparison values for the
incremental counter function block, as well as a start value.
There are 2 incremental counter available.
The maximum counter frequency for easy800 standard is 3000 Hz and
5000 Hz for EASY806-DC-SWD.
Contacts and Coils
Example of a high-speed incremental counter
Figure 119:Wiring the function block coils
The count inputs of function block CI01 are already permanently assigned to
device inputs I1 and I2. The coils of the function block are connected directly
here to the device inputs.
→
Square wave count pulses are required to ensure a 1:1 mark to
space ratio.
The signals of channels A and B must be offset by 90°
otherwise the count direction will not be detected.
→
Note that the digital inputs I1 to I4 are permanently assigned to
the incremental counter function blocks provided:
•
I1: Counter input for counter CI01, channel A.
•
I2: Counter input for counter CI01, channel B.
•
I3: Counter input for counter CI02, channel A.
•
I4: Counter input for counter CI02, channel B.
Contacts
Meaning
CI..OF
Reaching or exceeding the upper limit setpoint
CI..FB
Reaching or falling below the lower limit setpoint
CI..ZE
Actual value equals zero
CI..CY
Value range exceeded
Coils
Function
CI..EN
Selective activation of the function block
CI..RE
Reset the actual value to zero
CI..SE
Transfer of the start value on a rising edge.
I 05---------------------------
Ä
CI01EN
I 06---------------------------
Ä
CI01RE
I 07---------------------------
Ä
CI01SE
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...