3 Commissioning
3.10 Commissioning an Net network
94
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
Changing the station list although all NET-IDs are assigned
If all eight NET-IDs are assigned, the NET-IDs that are to be assigned to other
geographical positions must be switched to zero. A trick can be used to
simplify this:
If the NET-ID of a geographical position is set to 0 in the station list, the
NET-IDs of all subsequent positions are likewise set to 0.
Example: NET-ID (= 2) of geographical position 3 is set to 0
3.10.2 Configuring NET
Once you have completed the parameter assignment of the NET stations
and created a station list, you can then configure the easyNet. For the
configuration, all devices connected on the NET are assigned their NET ID in
the order in which they were entered in the station list in the STATION
menu. Furthermore, all devices are automatically set with the baud rate and
bus delay time set on NET station 1.
Carry out this configuration in the CONFIGURE menu.
You can only configure the NET network by entering settings on the
NET station 1.
physical
position
NET-ID
physical
Position
NET-ID
1
1
1
1
2
7
2
7
3
6
3
0
4
4
4
0
5
5
5
0
6
3
6
0
7
2
7
0
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...