12 Appendix
12.3 Technical data
360
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
12.3.8 SmartWire-DT
SWD power supply
(generated from the POW supply voltage)
easy800-SWD
Rated operational voltage
U
e
V
14.5
g
3 %
Current
1)
I
max
A
EASY802-DC-SWD: 0.4
EASY806-DC-SWD: 0.7
Short-circuit strength
yes
Potential isolation
from power supply, POW, inputs, outputs
no
to easyNet
yes
to the PC interface (COM)
yes
SWD-line
Number of SWD stations
max. 99
Maximum length of SWD line
m
max. 600
Baud Rate
kBd
125/250
Physics of the data cable
RS485
Address setting
Automatically via Configuration button
Status display
Multi-color SWD-LED: orange/green/red
Dual colored Config LED: green/red
Connections
Plug, 8-pole
Plug connectors
Blade terminal SWD4-8MF2
Bus termination
Integrated in the device
The end of the SWD line must be
terminated with: SWD-RC8-10
1) If SWD components with a higher total power consumption are connected, an EU5C-SWD-PF2 power feed
module must be used.
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...