2 Installation
2.6 Connecting outputs
46
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
Note that only outputs of the same group can be connected in parallel.
Groups are
•
Q1 to Q4
•
Q5 to Q8
•
S1 to S4
•
S5 to S8
Outputs connected in parallel must be switched at the same time.
2.6.1 Connect relay outputs
Connecting relay outputs of the
800 standard
Figure 45:Relay outputs EASY8..-..RC.
DANGER
Only outputs of the same group (S1 to S4 or S5 to S8) can be
connected in parallel; e.g. S1 and S3 or S5, S7 and S8. Outputs
connected in parallel must be switched at the same time.
DANGER
Do not exceed the maximum voltage of 250 V AC on a relay
contact. If the voltage exceeds this threshold, flashover may
occur at the contact, resulting in damage to the device or a
connected load.
+ 24 V
H
0 V
H
, N
F
8 A/B 16
L1, L2, L3 (115/230 V
h
)
25 000
R
L
24 V
H
8 A
115 V
h
8 A
230 V
h
8 A
2 A
2 A
2 A
1000 W
10
x
58 W
1 2
2
2
2
2
2
1
1
1
1
1
10 000 000
Q6
Q5
Q4
Q3
Q2
Q1
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...