6 The network Net
6.4 Network transmission security
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
281
The default settings for the input and output devices are:
6.4 Network transmission security
easyNet is a CAN-based network with the same error detection capability as
CAN. A BOSCH study relating to undiscovered and corrupt messages
determined the following:
The probability of non-discovery of a corrupted message (residual error
probability) is:
< 10
–10
message error rate.
The message error rate depends on:
•
Bus loading
•
Telegram length
•
Malfunction frequency
•
Number of stations
Example using a network with:
•
500 Kbaud
•
average bus load 25 %
•
average operating time 2000 h/year
•
average error rate of 10
–3
, i.e.: 1 message is faulty every 1000
•
transmission of 1.12
-
10
10
messages per year of which 1.12
-
10
7
messages are faulty
•
Residual error probability: r < 10
–10
-
10
–3
= 10
–13
This means: one of 10
13
messages is so corrupt that the fault cannot be
recognised as such. For a network, this corresponds to a working time of
approx. 1000 years.
SEND IO
å
REMOTE RUN
å
REMOTE IO
å
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...