3 Commissioning
3.8 The first circuit diagram
78
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
3.8 The first circuit diagram
The following provides a step by step example of how to wire your first
circuit diagram. In this way you will learn all the rules, quickly enabling you to
use an easy800 device for your own projects.
As with conventional wiring, you use contacts and relays in the diagram.
The easy800 device saves you having to use and wire different components.
At the push of a few buttons, the easy800 circuit diagram produces all the
wiring required. All you have to do is then connect any switches, sensors,
lamps or contactors you wish to use.
3.8.1 Switching to the circuit diagram
Requirements for circuit diagram entry:
The easy800 device is not in STOP mode. They are in the Status display.
▶
Press OK to move from the Status display to the main menu.
The PROGRAM menu option must then be selected on the easy800 device.
In general, press OK to switch to the next menu level, and press ESC to
move one level back.
▶
Press OK twice to enter the circuit diagram display via menu options
PROGRAM… -> CIRCUIT DIAGRAM. This is where you will create the
circuit diagram.
Circuit diagram display
The content of the circuit diagram is displayed in the first three lines.
This window can be moved over the circuit diagram. At the moment the
circuit diagram is empty. The cursor flashes at the top left, which is where
you will start to wire your circuit diagram.
The last line indicates the position of the cursor:
•
L: = Rung (
L
ine)
•
C: = Contact or coil field (
C
olumn)
•
B: = Amount of free memory in
B
ytes
I...............
I
P-
MO 02:00
Q
PROGRAM...
STOP
å
RUN
PARAMETER
SET CLOCK...
CIRCUIT DIAGRAM
FUNCTION BLOCKS
Ê
L: 1 C:1 B:7944
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...