3 Commissioning
3.10 Commissioning an Net network
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
93
3.10.1.2 Change station list
You can change the NET configuration at any time via the NET station with
the geographical position 1. Existing NET-IDs can only be changed to free
NET-IDs that have not yet been assigned.
▶
Move in the station list to the geographical position to which you wish to
assign another NET-ID. (
Section 3.10.1.1, “Creating the station list“
on Page 92).
▶
Press the OK pushbutton.
▶
Select the required NET ID with the
Í
and
Ú
cursor buttons and confirm
your input with the OK pushbutton.
▶
Configure NET stations again using the CONFIGURATION menu,
If your NET configuration does not function as required you will find a
description of possible causes in
section “Functionality of the NET
CAUTION
Operating the NET with two masters (two stations with NET-ID
1) is not allowed, and leads to malfunctions on the NET.
Possible effects of this type of incorrect configuration with two
masters competing against each other, and in which one is
operated in the STOP operating mode and the other in the RUN
operating mode, are as follows:
NET stations with NET-ID 2 - 8 that should follow the operating
mode changes of the NET station with NET-ID 1 automatically
during operation (REMOTE RUN parametric programming) keep
toggling constantly between the STOP and RUN operating
states.
When integrating a master that is already configured into an
existing NET, please make sure that there is no other station
with NET-ID 1 on the NET.
Tip: Carry out a NET configuration through NET station 1 after
every change to the NET.
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...