In this case, the actual configuration matches the target configuration.
11.5 Functionality of the NET faulty
Table 24: Checking the functionality of the NET using the NET LED
Config-LED
Meaning
Green flashing
A station of the project configuration was replaced by a compatible station in the target
configuration. The replacement is permitted by the “Compatible devices permissible”
device parameter being clicked.
red continuous light
Configuration error: the target configuration does not match the project configuration.
Possible causes:
• The SWD station of the project configuration was replaced by a incompatible station.
• SWD station was replaced by a compatible station, but the “Compatible devices
permissible” device parameter has not been clicked.
• The station was replaced by an universal module, but the “Replaceable with
universal module” device parameter has not been clicked
CAUTION
You can make a visual check the functionality of the NET by
means of the NET LED and in the circuit diagram via diagnostics
bit ID01-ID08.
Status of the NET
LED
Meaning
Off
NET not operational, fault in configuration
Continuous light
NET station fault, possible causes:
• Net is initialized and at least one station has not been detected. Check the plug-in
connections.
• You have modified the NET ID or baud rate for at least one station after the
configuration has been completed. Change the configuration.
• You have deleted
the program
on a NET station and thus also its NET configuration,
Page 94. Recon
fi
gure the NET via station 1.
• You have expanded an existing NET station and replaced it with a new device which
cannot be assigned parameters.
Flashing
NET operating fault-free
Event
Explanation
Remedy
easy800 standard cannot
configure EC4P easyControl
devices reliably (NET
parameters).
Synchronization between the devices
Set the NET parameters directly
on the EC4P.
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...