Dead Bus Synchronising (Auto Mode)
87
7.2 DEAD BUS SYNCHRONISING
During Dead bus synchronising a Start is issued from Mains control panel
Status
Excitation Delay
00:03
L-N V
A
L-L V
kW
50 Hz
Pf
7.3 HARDWARE REQUIREMENTS
•
DSE8610 V5.0 controller or higher.
•
DC controlled generator breaker.
•
Auxiliary contact to feed back generator breaker status to the DSE controller.
•
External relay driven by the DSE module to control the excitation of the alternator.
Status
Start Delay
00:00 s
Status
Fuel
Status
Crank Attempt
Status
Excitation Ramp
L-N V
A
L-L V
kW
Hz
Pf
Status
On Load
Excitation output closed voltage
rises to nominal settings.
Once the voltage and frequency
are within configurable limits the
set(s) can take load.
The Generator Breaker is closed ,
Excitation is switched off, start delay if
configured.
Fuel Output Activated
Engine Cranked
Excitation delay before excitation output
is activated. Generators run up to speed
if any on the MSC are out of limits they
are instructed to open their breaker and
synchronise in the normal manner.
Содержание DSE8610
Страница 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Страница 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Страница 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Страница 100: ...Protections 100 8 8 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4...
Страница 118: ...Intentionally Left Blank 118...