4 INSTALLATION
The DSE8600 Series module is designed to be mounted on the panel fascia. For dimension and
mounting details, see the section entitled
Specification, Dimension and mounting
elsewhere in this
document.
4.1 TERMINAL DESCRIPTION
4.1.1 DC SUPPLY, FUEL AND START OUTPUTS
Icon
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
1
DC Plant Supply Input
(Negative)
2.5mm²
AWG 13
2
DC Plant Supply Input
(Positive)
2.5 mm²
AWG 13
(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and
Output relays E - K
3
Emergency Stop Input
2.5mm²
AWG 13
Plant Supply Positive. In addition, supplies outputs 1 &
2.
(Recommended Maximum Fuse 20A)
4
Output relay A (FUEL)
2.5mm²
AWG 13
Plant Supply Positive from terminal 3. 15 Amp rated.
Fixed as FUEL relay if electronic engine is not
configured.
5
Output relay B (START)
2.5mm²
AWG 13
Plant Supply Positive from terminal 3. 15 Amp rated.
Fixed as START relay if electronic engine is not
configured.
6
Charge fail / excite
2.5mm²
AWG 13
Do not connect to ground (battery negative).
If charge alternator is not fitted, leave this terminal
disconnected.
7
Functional Earth
2.5mm²
AWG 13
Connect to a good clean earth point.
8
Output relay E
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
9
Output relay F
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
10
Output relay G
1.0mm²
AWG 18
Plant Supply Positive. from terminal 2. 3 Amp rated.
11
Output relay H
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
12
Output relay I
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
13
Output relay J
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
NOTE: Terminal 14 is not fitted to the DSE8600 series controller.
NOTE: When the module is configured for operation with an electronic engine, FUEL and
START output requirements may be different. Refer to
Electronic Engines and DSE Wiring
for
further information. DSE Part No. 057-004.
Содержание DSE8610
Страница 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Страница 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Страница 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Страница 100: ...Protections 100 8 8 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4...
Страница 118: ...Intentionally Left Blank 118...