Specifications
17
3.6.2.3
CLOSING COILS
For continuous closing signals (close signal is present continuously when the breaker is closed), follow
the instructions above as for
Contactor Coils
.
For momentary (pulsed) closing signals, use OUTPUT D, the normally open relay:
3.6.2.4
OPENING COILS / SHUNT TRIP COILS
For Continuous opening signal, use output D, the normally open relay:
For momentary (pulsed) closing signals, use a normally open relay:
3.6.2.5
OUTPUTS E,F,G,H, I & J
Number
6
Type
Fully configurable, supplied from DC supply terminal 2.
Rating
3A resistive @ 35V
Generator
When the DSE module requires the breaker closed, the output energises (closing the internal
relay) for the period of the Breaker Close Pulse timer after which the output is de-energised
(opening the internal relay).
Generator:
When the DSE module requires the breaker open, the output energises (closing the internal
relay).
Generator:
When the DSE module requires the breaker open, the output energises (closing the internal
relay) for the period of the
breaker trip pulse
.
Содержание DSE8610
Страница 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Страница 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Страница 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Страница 100: ...Protections 100 8 8 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4...
Страница 118: ...Intentionally Left Blank 118...