Description Of Controls
65
5.3.6 RS232 SERIAL PORT
This section is included to give information about the RS232 serial port and external modem (if
connected).
The items displayed on this page will change depending upon configuration of the module. You are
referred to your system supplier for further details.
NOTE: Factory Default settings are for the RS232 port to be enabled with no modem
connected, operating at 19200 baud, modbus slave address 10.
Example 1 – Module connected to an RS232 telephone modem.
When the DSE8610 series module is power up, it will send ‘initialisation strings’ to the connected
modem. It is important therefore that the modem is already powered, or is powered up at the same
time as the DSE86xx series module. At regular intervals after power up, the modem is reset, and
reinitialised, to ensure the modem does not ‘hang up’.
If the DSE8610 series module does not correctly communicate with the modem, “Modem initialising’
appears on the Serial Port instrument screen as shown overleaf.
If the module is set for “incoming calls” or for “incoming and outgoing calls”, then if the modem is
dialled, it will answer after two rings (using the factory setting ‘initialisation strings)’. Once the call is
established, all data is passed from the dialling PC and the DSE8610 series module.
If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module will dial
out whenever an alarm is generated. Note that not all alarms will generate a dial out; this is dependant
upon module configuration of the event log. Any item configured to appear in the event log will cause a
dial out.
Press down
to view the modem status....
Indicates that a modem is configured. Shows
‘RS232’ if no modem is configured.
Содержание DSE8610
Страница 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Страница 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Страница 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Страница 100: ...Protections 100 8 8 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4...
Страница 118: ...Intentionally Left Blank 118...