![DSEGenset DSE8610 Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/dsegenset/dse8610/dse8610_operators-manual_2535081044.webp)
Installation
44
4.1.9 RS485 CONNECTOR
PIN No
NOTES
A
Two core screened twisted pair cable.
120
Ω
impedance suitable for RS485 use.
Recommended cable type - Belden 9841
Max distance 1200m (1.2km) when using Belden 9841 or direct equivalent.
B
SCR
4.1.10 RS232 CONNECTOR
PIN No NOTES
1
Received Line Signal Detector (Data Carrier Detect)
2
Received Data
3
Transmit Data
4
Data Terminal Ready
5
Signal Ground
6
Data Set Ready
7
Request To Send
8
Clear To Send
9
Ring Indicator
View looking into the male connector on the 8600 series module
Location of RS232
connector
Location of RS485 connector