Operation
84
6.6.3 ENGINE RUNNING
In manual mode, the load is not transferred to the generator unless a ‘loading request’ is made.
A loading request can come from a number of sources.
•
Pressing the
transfer to generator
button.
•
Request from DSE8660 mains controller or from another DSE8610 controller over the MSC
link.
•
Activation of an auxiliary input that has been configured to
remote start on load
•
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE: The load transfer signal remains inactive until the Oil Pressure has risen. This
prevents excessive wear on the engine.
If the common bus is measured to be ‘dead bus’, the load breaker is closed.
If the bus is measured to be ‘live bus’, synchronising takes place before the breaker is closed.
Once the load has been transferred to the generator, the load switch will not be automatically opened
unless:
•
Press the
Open Generator
button (DSE8610/DSE8610 only)
•
Press the
auto mode
button to return to automatic mode.
6.6.4 MANUAL FUEL PUMP CONTROL
•
Navigate to the instruments page using the
buttons and locate FUEL LEVEL.
is
shown on the module display to indicate that this feature is available.
•
Press and hold the
button to energise the transfer pump. The pump starts two seconds
after the button is pressed.
•
Release the
button to de-energise the transfer pump.
Содержание DSE8610
Страница 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Страница 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Страница 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Страница 100: ...Protections 100 8 8 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4...
Страница 118: ...Intentionally Left Blank 118...