![DSEGenset DSE8610 Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/dsegenset/dse8610/dse8610_operators-manual_2535081043.webp)
Installation
43
4.1.7 CONFIGURABLE DIGITAL INPUTS
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
60
Configurable digital input A
0.5mm²
AWG 20
Switch to negative
61
Configurable digital input B
0.5mm²
AWG 20
Switch to negative
62
Configurable digital input C
0.5mm²
AWG 20
Switch to negative
63
Configurable digital input D
0.5mm²
AWG 20
Switch to negative
64
Configurable digital input E
0.5mm²
AWG 20
Switch to negative
65
Configurable digital input F
0.5mm²
AWG 20
Switch to negative
66
Configurable digital input G
0.5mm²
AWG 20
Switch to negative
67
Configurable digital input H
0.5mm²
AWG 20
Switch to negative
68
Configurable digital input I
0.5mm²
AWG 20
Switch to negative
69
Configurable digital input J
0.5mm²
AWG 20
Switch to negative
70
Configurable digital input K
0.5mm²
AWG 20
Switch to negative
4.1.8 PC CONFIGURATION INTERFACE CONNECTOR
DESCRIPTION
CABLE
SIZE
NOTES
Socket for connection to PC with
86xx series PC software.
0.5mm²
AWG 20
This is a standard USB
type A to type B connector.
NOTE: The USB connection cable between the PC and the 8600 series module must not
be extended beyond 5m (yards). For distances over 5m, it is possible to use a third party USB
extender. Typically, they extend USB up to 50m (yards). The supply and support of this type of
equipment is outside the scope of Deep Sea Electronics PLC.
CAUTION! Care must be taken not to overload the PCs USB system by connecting more
than the recommended number of USB devices to the PC. For further information, consult your
PC supplier.
CAUTION! This socket must not be used for any other purpose.
This configuration cable
is the same as normally
used between a PC and
a USB printer!
Содержание DSE8610
Страница 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Страница 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Страница 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Страница 100: ...Protections 100 8 8 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4...
Страница 118: ...Intentionally Left Blank 118...