![DSEGenset DSE8610 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/dsegenset/dse8610/dse8610_operators-manual_2535081022.webp)
Specifications
22
3.8.5 RS485
The RS485 port on the DSE8600 series controller supports the Modbus RTU protocol.
The DSE Gencomm register table for the controller is available upon request from the DSE Technical
Support Department.
RS485 is used for point-to-point cable connection of more than one device (maximum 32 devices) and
allows for connection to PCs, PLCs and Building Management Systems (to name just a few devices).
One advantage of the RS485 interface is the large distance specification (1.2km when using Belden
9841 (or equivalent) cable. This allows for a large distance between the DSE8600 series module and
a PC running the DSE Configuration Suite software.
The operator is then able to control the module,
starting or stopping the generator, selecting operating modes, etc.
The various operating parameters (such as output volts, oil pressure, etc.) of the remote generator
can be viewed or changed.
NOTE: For a single module to PC connection and distances up to 6m (8yds) the USB
connection method is more suitable and provides for a lower cost alternative to RS485 (which
is more suited to longer distance connections).
Recommended PC Serial Port add-ons (for computers without internal RS485 port).
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
•
Brainboxes PM154 PCMCIA RS485 card (for laptops PCs)
Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’
•
Brainboxes VX-023 ExpressCard 1 Port RS422/485 (for laptops and
nettop PCs)
•
Brainboxes UC320 PCI Velocity RS485 card (for desktop PCs)
Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’
•
Brainboxes PX-324 PCI Express 1 Port RS422/485 (for desktop PCs)
Supplier:
Brainboxes
Tel:
+44 (0)151 220 2500
Web:
http://www.brainboxes.com
Email:
Sales:[email protected]
NB
DSE Have no business tie to Brainboxes. Over many years, our own engineers have used these
products and are happy to recommend them.
Содержание DSE8610
Страница 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Страница 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Страница 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Страница 100: ...Protections 100 8 8 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4...
Страница 118: ...Intentionally Left Blank 118...