DSE 4 Steps To Successful Synchronising
114
14 DSE 4 STEPS TO SUCCESSFUL SYNCHRONISING
Synchronising and load sharing is often considered to be a complex subject. In fact, it is very simple
when broken down into smaller steps.
After following the
Commissioning
section of this manual, the
4 Steps
must
be followed before any
parallel operation is attempted.
The following information is a
short form
guide only, intended as a memory jogger once the steps are
fully understood.
The full video presentation of the
4 Steps
is available on the DSE website. www.deepseaplc.com.
Registration on the website is required. This is free of charge, along with all other downloads.
This page is also available as a training document (handout style) from DSE. Part Number 056-001
Four Steps to Synchronising – included on the DSE website.
14.1 CONTROL
Check the control of the engine is working:
•
Control of AVR
•
Control of Governor
•
Direction of Control
Failure of the above steps will result in poor control of the governor/AVR leading to problems
during synchronising and/or load sharing if not corrected.
14.2 METERING
•
CTs on the Right Phase
•
CTs in the Right Direction
Failure of the above steps will result in incorrect power factor and kW calculations leading to
problems load sharing if not corrected.
14.3 COMMUNICATIONS
•
All Modules Connected on the MSC Link
•
Re-Calibrate, Sync + Load Control, Multi-Set
•
Remove One MSC Plug
Failure of the above steps will result in the controllers being unable to communicate leading to
problems during synchronising and/or load sharing if not corrected.
14.4 SYNC CHECKS
•
Use the Built in Sync Scope to Determine Correct Phase Wiring
•
Phase Checks across the Breaker.
Failure of the above steps will result in serious damage to the system (breakers, bus bars,
alternators, engines etc)
Содержание DSE8610
Страница 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Страница 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Страница 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Страница 100: ...Protections 100 8 8 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4...
Страница 118: ...Intentionally Left Blank 118...