![DSEGenset DSE8610 Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/dsegenset/dse8610/dse8610_operators-manual_2535081080.webp)
Operation
80
6.4.1 ECU OVERRIDE
NOTE: Depending upon system design, the ECU may be powered or unpowered when the
module is in STOP mode. ECU override is only applicable if the ECU is unpowered when in
STOP mode.
When the ECU is powered down (as is normal when in STOP mode), it is not possible to read the
diagnostic trouble codes or instrumentation. Additionally, it is not possible to use the engine
manufacturers’ configuration tools.
As the ECU is usually unpowered when the engine is not running, it must be turned on manually as
follows:
•
Select STOP
mode on the DSE controller.
•
Press and hold the START
button to power the ECU. As the controller is in STOP mode,
the engine will not be started.
•
Continue to hold the start button for as long as you need the ECU to be powered.
•
The ECU will remain powered until a few seconds after the START button is released.
This is also useful if the engine manufacturer’s tools need to be connected to the engine, for instance
to configure the engine as the ECU needs to be powered up to perform this operation.
Содержание DSE8610
Страница 47: ...Installation 47 4 2 2 3 PHASE 4 WIRE WITHOUT EARTH FAULT PROTECTION...
Страница 51: ...Installation 51 4 3 2 SINGLE PHASE WITHOUT EARTH FAULT...
Страница 53: ...Installation 53 4 3 4 2 PHASE L1 L2 3 WIRE WITHOUT EARTH FAULT...
Страница 55: ...Installation 55 4 3 6 2 PHASE L1 L3 3 WIRE WITHOUT EARTH FAULT MEASURING...
Страница 100: ...Protections 100 8 8 1 EARTH FAULT TRIPPING CURVES NOTE DSE Factory setting is time multiplier K 0 4...