Digital Monitoring Products
XTLplus International Series Installation and Programming Guide
48
Wireless
- 1100INT Series Wireless options.
Contact
- Indicates if the Universal Transmitter is programmed to use the internal or external contact.
External Contact N/O?
- Identifies whether externally installed contacts are programmed as a normally open (N/O)
or normally closed (N/C) circuit. Y = N/O Contacts. N = N/C Contacts.
Supervision Time
- Selects the number of minutes for DMP wireless supervision.
1142INT LED Operation
- Identifies DMP 1142INT Wireless Two-Button transmitter LED operation.
Disarm/Disable -
Disables Zone Tripped messages.
Message
- A = alarm report, T = trouble report,
L = local with no report, — (dash) = no report.
Output
- 51 to 54 and 61 to 64 wireless outputs or wireless key fob zones.
Action
- This selects the type of relay output:
S = steady, P = pulse, M = momentary, and F = follow
Swinger Bypass
- The zone can be automatically bypassed after a programmed number of trips.
Prewarn
- This selects the keypad address that sounds the entry prewarn for this zone.
Entry Delay
- Selects the entry delay timer used
for this zone.
Priority
- Requires this zone to be in a normal condition before the area can be armed.
Traffic Count -
Provides the number of zone trips per area for Night and Exit type zones in a disarmed state.
Zone Audit Days -
Number of days allowed to elapse without a zone being tripped before a message is sent.
Receiver Routing -
This selects the routing option for Auxiliary 1 or Auxiliary 2 zone types.
Style
- The abbreviations that display on the keypad for arming zone style. TGL = Toggle,
ARM = Arm only, DIS = Disarm only
STEP = Wireless arming, MNT = Maintain
Common Keypad Messages
Message
Meaning
Possible Solutions
INVALID CODE
The user code you have entered is not
recognized by the system.
Check the user code and try again.
CLOSING TIME
The schedule has expired but the system
has not been armed.
Users still on the premise should arm the system or
extend the schedule to a later time.
KEYPAD NAME - NOPWR
Wireless keypad is not getting proper
power.
Check that AC/DC transformer is plugged in correctly.
AC TROUBLE
The system AC is low or missing.
Check that the AC connections are good.
BATTERY TROUBLE
The System battery is either low or missing.
Check that the battery connections are good and the
battery is still good.
SYSTEM TROUBLE or
SERVICE REQUIRED
There is a problem with one or more
components in the system.
Press the RESET button for 1-2 seconds.
SYSTEM BUSY
The system is performing another task with
a higher priority.
Wait a few moments for the system to complete the
task. If the message displays for a long period of time,
the processor could be locked up.
TRANSMIT FAIL
The panel has attempted to communicate
with the central station 10 times and has not
succeeded.
Verify your communication type, account number, and
IP address.
ENTER CODE (When
entering Programming)
A lockout code has been programmed for
the panel.
Enter the lockout code.