Digital Monitoring Products
XTLplus International Series Installation and Programming Guide
46
Trip Counter For DMP Wireless Test (WLS)
Displays the number of wireless zones that automatically communicate a supervisory
check-in message. The test will run for a total of 5 minutes. During the 5 minutes
the transmitters are being tested multiple times. In order for a transmitter to pass it
must have checked in 3 or more times. At the end of the 5 minutes the results will be
displayed. A timer will be displayed at the keypad to indicate that the test is in progress.
The results will display which transmitters have failed the test.
The number of zones that check in. (XXX in the example).
• The total number of wireless zones programmed for supervision that should check in.
(ZZ in the example).
END -
Select END to stop the Wireless Test. When the test ends or a 20-minute time-
out expires, normal wireless zone processing returns. If all transmitters check-in, both
numbers will match within three (3) minutes. If a transmitter has multiple zones (1101,
1114, etc.), all zones will be included in the counts. Failed wireless zones then display on
the keypad.
Test End Warning
When no zones have been tripped and five minutes remain on the 20 minute Walk Test
timer, the keypad displays
TEST END WARNING
and the keypad tones. If no additional test
zone trips occur, the test ends and a final Sensor Reset automatically occurs. The System
Test End message is sent to the receiver along with Verify and Fail messages for each zone
under WALK test. Faulted zones then display on the keypad.
Failed Zones Display
Each zone that did not trip at least once during the Walk Test displays on the keypad that
initiated the test. Any Fire (FI), Panic (PN), Supervisory (SV), or Carbon Monoxide (CO) 24-
hour zone that is faulted at the end of the Walk Test displays a trouble condition for that
zone regardless of the message programmed for the open or short condition of the zone
and a zone trouble is sent to the receiver. Press
CMD
to display the next failed zone.
For the Wireless Test, failed wireless zones display only on the keypad. Zone Verify/Fail
reports are not sent to the central station receiver for the wireless checkin test.
Keypad Speaker Operation
When using LCD Keypads, the panel provides distinct speaker tones from the keypad for Fire, Burglary, Zone
Monitor, and Prewarn events. The list below details the conditions under which the speaker is turned on and
off for each event.
Fire
On
- Fire zone alarm and Bell Output or Fire Bell Output is ON.
Off
- Alarm Silence.
Burglary
On
- Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
Off
- Alarm Silence.
Zone Monitor
On
- One time only when a monitored zone is tripped.
Off
- After one tone.
CO
On
- CO zone alarm and Bell Ouput are ON.
Off
- Using Sensor Reset option while no additional CO type zones are in alarm.
Prewarn
On
- During Entry Delay.
Off
- When Entry Delay expires.
TRIPS: XXX
END
TEST END WARNING
ZONE: 10
-FAIL
SOUTH LOBBY