XTLplus International Series Installation and Programming Guide
Digital Monitoring Products
45
Wi-Fi Signal Strength
Number of Bars
Indication
7
Good Signal
(Excellent for consistent operation)
6
5
4
Average Signal
(Expect consistent operation)
3
2
1
Weak Signal
(Will not operate reliably. Relocate Wi-Fi
equipment or add a Wi-Fi extender for better reception.)
0
No Signal
Z-Wave Test Option
This feature allows the installer to test XTLplusINT communication with Z-Wave
devices. A successful test indicates a response from a device. Press any select area
to view the Z-Wave Device List.
Press
CMD
to advance through each Z-Wave device and press any select area to
begin the test on the device displayed.
The name of the device displays above the device number. The current number of
successful communications followed by the total number of attempts displays to
the right of the device number. The test stops after 99 attempts.
Press
CMD
to view the final number of successful communications.
Initializing Z-Wave Defaults
Only use this function when the Z-Wave network primary controller is missing or otherwise inoperable.
1. Rest the panel and enter
2313
(DIAG) at the keypad to access the Diagnostic menu.
2. Press
CMD
until
INIT Z-WAVE
displays and press a top row select key or area.
3. Select
YES
when
Z-WAVE? NO YES
displays.
INIT SUCCESSFUL
displays when all Z-Wave
programming has been initialized
Exiting the Diagnostics Menu
Press
CMD
until
STOP
displays. Press any select area. The keypad returns to the Status List display.
Using the Walk Test
The XTLplusINT panel provides a walk test feature that allows a single technician to test all the protection devices
connected to zones on the system. Conduct the Walk Test within 30 minutes of resetting the panel. The Walk Test
automatically ends if no zones are tripped for 20 minutes.
TEST IN PROGRESS
displays at all keypads. When five
minutes remain,
TEST END WARNING
displays. If any areas are armed the Walk Test does not start and
SYSTEM
ARMED
displays.
Walk Test
To conduct the Walk Test, reset the control panel by pressing the RESET button then
wait one minute. From the keypad, enter the code 8144. The keypad displays
WALK
TEST
.
STD
(Standard Walk Test) - Select STD to Walk Test zones. All programmed zones are
included in the test.
WLS
(Wireless Test) - Select
WLS
to automatically test 1100INT Series wireless
transmitter communications. Includes all wireless devices except key fobs and
transmitters programmed for a supervision time of 0 (zero).
PIR
(Wireless PIR Walk Test) - The PIR Walk Test allows the installer to verify the 1122INT
PIR and 1128INT operation. When enabled, the LED flashes each time motion is detected for
up to 30 minutes. This is a local test only and no messages are sent to the Central Station.
HALLWAY LIGHT
LIGHT 02 0/0
TEST ZWAVE
DEVICE LIST:
HALLWAY LIGHT
HALLWAY LIGHT
99/99 SUCCESSFUL
WALK TEST