MIL-3000FTX Series of FastPort Print Servers
E-1
A p p e n d i x E
Troubleshooting AppleTalk
E.1 Troubleshooting Tips
The following are troubleshooting tips for AppleTalk.
E.1.1 Reset Time
The default for reset time may have to be changed. The reset time is the
amount of time FastPort waits before sending the next print job to a printer.
Since reset times for the printers vary greatly, FastPort uses values
specified by the variables
Wait Time Before Reset
and
Wait Time
After Reset
to delay sending print jobs before and after a reset sequence.
These are set via the
SetUp Defaults
file (see “Using Setup Defaults
File” on page 6-4).
E.1.2 Configuration to Use the ACK Signal
FastPort relies on the ACK signal from the printer. Sometimes printers
require the use of more signals (for example,
Busy
) to send correctly on the
interface. If the unit is having parallel flow control problems, modify the
flow control method (see “Using Setup Defaults File” on page 6-4).
E.1.3 Situation 1: Printing Over Ethertalk Using Driver 7.x
The serial port fails when the user tries to print over EtherTalk using driver
7.x to LaserWriter printers. For bi-directional printing support across the
serial interface (for LaserWriter II and II NT printers), use the following
procedure. The printer needs to be initialized with correct data and parity
values. Do this by either making a telnet connection into the serial port of
FastPort or connecting a terminal to the printer’s serial port.
1. Turn the LaserWriter off and set the front panel switches D1 and D2
down. This sets the Laser Writer in PS Batch Mode with these values for
RS-232 set for 9600 baud, RS-422 set for 9600 baud with port values of 7
data bits, no parity check, 1 stop bit, and Xon/Xoff.
2. Turn on the LaserWriter. It prints a test page with current settings.