Figure 10.25.
Analog Input controlling "Relay 1" examples
On the figure above, it is illustrated how Analog Input changes reflect to Relay 1 with settings
from
Figure 10.24
. The log messages are written on any alarm event (LOW ALARM event and
HIGH ALARM event respectively) but emails are sent only on HIGH ALARM event and MQTT
notifications are sent on HIGH ALARM event as well. The first two examples are captured with
Relay 1 configured to operate in "Normal"
Relay Switch Mode
(see
10.6.4 Relays
).
In "Normal"
Control Mode
Relay 1 (in our example) will be turned on when LOW ALARM event
is generated and will be turned off when HIGH ALARM event is generated.
In "Inversed"
Control Mode
Relay 1 will be turned on when HIGH ALARM event is generated
and will be turned off when LOW ALARM event is generated.
Last two graphics shows "Normal" and "Inversed"
Control
Mode
of the analog input combined
with Relay 1 operating in "Timer On" and "Timer Off"
Relay Switch Mode
. As seen in "Normal"
Control Mode
of the analog Input when
Relay Switch Mode
is "Timer Off", the relay turns on
Содержание smartDEN Opener
Страница 15: ...smartDEN Opener User Manual 24 Apr 2018 15 Figure 5 2 Distribution box version overview...
Страница 62: ...smartDEN Opener User Manual 24 Apr 2018 62 Figure 10 18 Digital input controlling relay examples...
Страница 80: ...smartDEN Opener User Manual 24 Apr 2018 80 10 7 General Settings Figure 10 32 General Settings page...
Страница 107: ...smartDEN Opener User Manual 24 Apr 2018 107 12 2 9 MQTT command reply Figure 12 2 MQTT successful response...
Страница 114: ...smartDEN Opener User Manual 24 Apr 2018 114 Figure 16 4 Relays Tab Figure 16 5 Main Controlled Device s modes...
Страница 116: ...smartDEN Opener User Manual 24 Apr 2018 116 Figure 16 8 GPS outside mode notification...