smartDEN Opener
User Manual
24 Apr 2018
- 67 -
High Alarm
- sets the scaled value on which HIGH ALARM event will be generated. HIGH
ALARM event is generated when the scaled value of the Analog Input is lower than
Low
Alarm
parameter value and then exceeds
High Alarm
parameter value;
Enable Alarm
- if this option is checked alarms will be generated for the analog input;
Send notification On
- this parameter allows sending notifications on specified alarm.
There are four choices:
o
Never
-
smartDEN Opener
will not send any notifications about analog input;
o
Low Alarm
- controller will send notifications only on LOW ALARM event;
o
High Alarm
- controller will send notifications only on HIGH ALARM event;
o
Any Alarm
- will send notifications on both LOW ALARM and HIGH ALARM events;
In order to use this parameter MQTT settings should be set properly and Admin/Guest
accounts should be enabled in the way desired.
Send Email On
- this parameter allows sending emails on specified alarm. There are three
identical to notifications choices:
o
Never
-
smartDEN Opener
will not send any emails about analog input;
o
Low Alarm
- controller will send emails only on LOW ALARM event;
o
High Alarm
- controller will send emails only on HIGH ALARM event;
o
Any Alarm
- will send emails on both LOW ALARM and HIGH ALARM events;
Log On
- this parameter allows writing to events log only on specified alarm. There are
same choices as emails and notifications:
o
Never
-
smartDEN Opener
will not write any logs about analog input;
o
Low Alarm
- controller will write logs only on LOW ALARM event;
o
High Alarm
- controller will write logs only on HIGH ALARM event;
o
Any Alarm
- will write logs on both LOW ALARM and HIGH ALARM events;
Controls
- this parameter specifies which output is controlled by the analog input. There
are four choices:
o
Nothing
- this analog input will not control any output. If some of the previous settings
are set it will be used for monitoring some process (for example if used humidity sensor
it may send notification when it reaches selected alarm);
o
Relay 1
- the analog input will control Relay 1;
o
Relay 2
- the analog input will control Relay 2;
o
Main
- the analog input will control Main Controlled Device;
Control Mode
(
Controls
is selected to be "Relay1" or "Relay2"):
o
Normal
- in this mode the selected relay will turn on when analog input generates HIGH
ALARM event and will turn off when LOW ALARM event is generated;
o
Inversed
- in this mode the selected relay will turn on when analog input generates LOW
ALARM event and will turn off when HIGH ALARM event is generated;
Control Mode
(
Controls
is selected to be "Main"):
o
Open
- in this mode Main Controlled Device will start
OPENING
on HIGH ALARM event
if not
OPENED
;
o
Close
- in this mode Main Controlled Device will start
CLOSING
on LOW ALARM event
if not
CLOSED
;
o
Open/Close
- in this mode Main Controlled Device will start
CLOSING
on LOW ALARM
event and will start
OPENING
on HIGH ALARM event;
o
Close/Open
- in this mode Main Controlled Device will start
OPENING
on LOW ALARM
event and will start
CLOSING
on HIGH ALARM event;
Save
- before leaving this tab or page click this button to changes take effect.
Содержание smartDEN Opener
Страница 15: ...smartDEN Opener User Manual 24 Apr 2018 15 Figure 5 2 Distribution box version overview...
Страница 62: ...smartDEN Opener User Manual 24 Apr 2018 62 Figure 10 18 Digital input controlling relay examples...
Страница 80: ...smartDEN Opener User Manual 24 Apr 2018 80 10 7 General Settings Figure 10 32 General Settings page...
Страница 107: ...smartDEN Opener User Manual 24 Apr 2018 107 12 2 9 MQTT command reply Figure 12 2 MQTT successful response...
Страница 114: ...smartDEN Opener User Manual 24 Apr 2018 114 Figure 16 4 Relays Tab Figure 16 5 Main Controlled Device s modes...
Страница 116: ...smartDEN Opener User Manual 24 Apr 2018 116 Figure 16 8 GPS outside mode notification...