smartDEN Opener
User Manual
24 Apr 2018
- 70 -
On
Figure 10.23
is illustrated how Analog Input changes reflect Main Controlled Device with
settings from
Figure 10.22
. MQTT notifications are sent and log messages are written on "Any
Alarm" (LOW ALARM event and HIGH ALARM event respectively) but emails are sent only on
HIGH ALARM event.
When
Control Mode
is set to "Open" the Main Controlled Device will start
OPENING
on every
generated HIGH ALARM event. It is shown that Main is in
CLOSED
state first. Then an
OPEN
command is sent from the web server and Main Controlled Device starts
OPENING
. It reaches
OPENED
state and accepts another
CLOSE
command. Main starts
CLOSING
and LOW ALARM
event is generated but this does not affect this
Control Mode
so Main Controlled Device
continuous
CLOSING
and goes to
CLOSED
state. When it is in state
CLOSED,
the Analog Input
generates HIGH ALARM event which starts
OPENING
the Main Controlled Device and it goes to
OPENED
state. No more alarms are generated after that.
In "Close" Control Mode the Main Controlled Device starts CLOSING on every LOW ALARM
event generated. In our example when the Main Controlled Device is in
CLOSED
state,
OPEN
command is sent from web server. The Main Controlled Device starts
OPENING
and goes to
OPENED
state. Lately, LOW ALARM event is generated and Main starts
CLOSING
and goes to
CLOSED
state. The next HIGH ALARM event generated will not affect the state in this mode.
In "Open/Close" Control Mode the Main Controlled Device is OPENED on every HIGH ALARM
event and
CLOSED
on every LOW ALARM event. As shown on
Figure 10.23
, Main Controlled
Device is
CLOSED
and
STOP
command is received from web server, which makes Main
Controlled Device to go in
STOPPED
state. When LOW ALARM event generated by the Analog
Input, Main Controlled Device starts
CLOSING
and goes to
CLOSED
state. Then a HIGH ALARM
event is generated and Main Controlled Device starts
OPENING
and goes to
OPENED
state.
In "Close/Open" Control Mode the Main Controlled Device is OPENED on every LOW ALARM
event and
CLOSED
on every HIGH ALARM event. Main Controlled Device is
CLOSED
and
STOP
command is received from web server which makes Main Controlled Device to go in
STOPPED
state. Then a
CLOSE
command is received from the web server and Main starts
CLOSING
. At
this moment, before Main Controlled Device's
Open/Close Time
expires,
LOW ALARM event is
generated, Main Controlled Device starts
OPENING
and goes to
OPENED
state. Lately HIGH
ALARM event is generated and Main Controlled Device starts
CLOSING
which makes it
CLOSED
.
Содержание smartDEN Opener
Страница 15: ...smartDEN Opener User Manual 24 Apr 2018 15 Figure 5 2 Distribution box version overview...
Страница 62: ...smartDEN Opener User Manual 24 Apr 2018 62 Figure 10 18 Digital input controlling relay examples...
Страница 80: ...smartDEN Opener User Manual 24 Apr 2018 80 10 7 General Settings Figure 10 32 General Settings page...
Страница 107: ...smartDEN Opener User Manual 24 Apr 2018 107 12 2 9 MQTT command reply Figure 12 2 MQTT successful response...
Страница 114: ...smartDEN Opener User Manual 24 Apr 2018 114 Figure 16 4 Relays Tab Figure 16 5 Main Controlled Device s modes...
Страница 116: ...smartDEN Opener User Manual 24 Apr 2018 116 Figure 16 8 GPS outside mode notification...