2.1.7 Initial Commissioning
The easiest way of carrying out the initial commissioning is
by using the [Quick Menu] key and follow the quick set-up
procedure using LCP 102 (read table from left to right).
The example applies to open loop applications.
Press
Quick
Menu
Q2 Quick Menu
OK
OK
Set language
OK
Set Motor nameplate power
OK
Set Nameplate voltage
OK
Set Nameplate frequency
OK
Set Nameplate current
OK
Set Nameplate speed in RPM
5-12 Terminal 27 Digital Input
OK
If terminal default is
Coast
inverse
it is possible to change
this setting to
No function
. No
connection to terminal 27 is
then needed for running AMA
1-29 Automatic Motor Adaptation
(AMA)
OK
Set desired AMA function.
Enable complete AMA is
recommended
OK
Set the minimum speed of the
motor shaft
OK
Set the maximum speed of the
motor shaft
OK
Set the ramping up time with
reference to synchronous
motor speed, n
s
OK
Set the ramping down time
with reference to synchronous
motor speed, n
s
OK
Set the site from where the
reference must work
Table 2.3
Another easy way of commissioning the drive is by using
the Smart Application Setup (SAS), which can also be
found under the Quick Menu. Follow the indications on
the successive screens for setting-up the applications
listed.
How to Programme
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
17
2
2