13-10 Comparator Operand
Array [6]
Option:
Function:
[183] Drive stopped
[183] Drive stopped
A stop command
(Jog, Stop, Qstop, Coast) is issued – and
not from the SLC itself.
[185] Drive in hand
mode
[185] Drive in hand mode
High when the
frequency converter is in hand mode.
[186] Drive in auto
mode
[186] Drive in auto mode
High when the
frequency converter is in auto mode.
[187] Start command
given
[190] Digital input x30
2
[191] Digital input x30
3
[192] Digital input x30
4
[193] Digital input x46
1
[194] Digital input x46
2
[195] Digital input x46
3
[196] Digital input x46
4
[197] Digital input x46
5
[198] Digital input x46
6
[199] Digital input x46
7
13-11 Comparator Operator
Array [6]
Option:
Function:
Select the operator to be used in the
comparison. This is an array parameter
containing comparator operators 0 to 5.
[0]
<
Select
[0] <
for the result of the evaluation to
be TRUE, when the variable selected in
is smaller than the
fixed value in
13-12 Comparator Value
. The
result will be FALSE, if the variable selected in
is greater than the
fixed value in
13-12 Comparator Value
.
[1]
*
≈ (equal)
Select
[1] ≈
for the result of the evaluation to
be TRUE, when the variable selected in
is approximately
equal to the fixed value in
13-12 Comparator
Value
.
[2]
>
Select
[2] >
for the inverse logic of option <
[0].
13-11 Comparator Operator
Array [6]
Option:
Function:
[5]
TRUE longer
than..
[6]
FALSE
longer
than..
[7]
TRUE
shorter
than..
[8]
FALSE
shorter
than..
13-12 Comparator Value
Array [6]
Range:
Function:
Size related
*
[-100000.000 -
100000.000 ]
Enter the ‘trigger level’ for the
variable that is monitored by
this comtor. This is an array
parameter containing comtor
values 0 to 5.
3.14.4 13-1* RS Flip Flops
The Reset-Set Flip Flops hold the signal until set/reset.
Par. 13-15
RS-FF Operand S
Par. 13-16
RS-FF Operand R
130BB959.10
Illustration 3.51
Two parameters are used and the output can be used in
the logic rules and as events.
R
S
Flip Flop Output
130BB960.10
Illustration 3.52
The two operators can be selected from a long list. As a
special case, the same digital input can be used as both
Set and Reset, making it possible to use the same digital
input as start/stop. The following settings can be used to
set up the same digital input as start/stop (example given
with DI32 but is not a requirement).
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
119
3
3
Содержание VLT AutomationDrive FC 300 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT AutomationDrive...
Страница 210: ...www danfoss com drives MG33ME02 130R0334 MG33ME02 Rev 2012 02 20...
Страница 211: ......