13-01 Start Event
Option:
Function:
[5]
Torque limit
[5] Torque limit
The torque limit, set in
or
4-17 Torque Limit Generator Mode
, has
been exceeded.
[6]
Current limit
[6] Current limit
The motor current limit,
set in
, has been
exceeded.
[7]
Out of current
range
[7] Out of current range
The motor
current is outside the range set in
[8]
Below I low
[8] Below I low
The motor current is
lower than set in
[9]
Above I high
[9] Above I high
The motor current is
higher than set in
.
[10]
Out of speed
range
[10] Out of speed range
The speed is
outside the range set in
and
.
[11]
Below speed low
[11] Below speed low
The output speed
is lower than the setting in
[12]
Above speed
high
[12] Above speed high
The output speed
is higher than the setting in
[13]
Out of feedb.
range
[13] Out of feedb. Range
The feedback is
outside the range set in
and
[14]
Below feedb. low
[14] Below feedb. Low
The feedback is
below the limit set in
.
[15]
Above feedb.
high
[15] Above feedb. High
The feedback is
above the limit set in
[16]
Thermal warning
[16] Thermal warning
The thermal
warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the
brake resistor or the thermistor.
[17]
Mains out of
range
[17] Mains out of range
The mains
voltage is outside the specified voltage
range.
[18]
Reversing
[18] Reversing
The output is high when
the frequency converter is running
counter clockwise (the logical product
of the status bits “running” AND
“reverse”).
13-01 Start Event
Option:
Function:
[19]
Warning
[19] Warning
A warning is active.
[20]
Alarm (trip)
[20] Alarm (trip)
A (trip) alarm is active.
[21]
Alarm (trip lock)
[21] Alarm (trip lock)
A (Trip lock) alarm
is active.
[22]
Comparator 0
[22] Comparator 0
Use the result of
comparator 0.
[23]
Comparator 1
[23] Comparator 1
Use the result of
comparator 1.
[24]
Comparator 2
[24] Comparator 2
Use the result of
comparator 2.
[25]
Comparator 3
[25] Comparator 3
Use the result of
comparator 3.
[26]
Logic rule 0
[26] Logic rule 0
Use the result of logic
rule 0.
[27]
Logic rule 1
[27] Logic rule 1
Use the result of logic
rule 1.
[28]
Logic rule 2
[28] Logic rule 2
Use the result of logic
rule 2.
[29]
Logic rule 3
[29] Logic rule 3
Use the result of logic
rule 3.
[33]
Digital input DI18
[33] Digital input DI18
Use the result of
digital input 18.
[34]
Digital input DI19
[34] Digital input DI19
Use the result of
digital input 19.
[35]
Digital input DI27
[35] Digital input DI27
Use the result of
digital input 27.
[36]
Digital input DI29
[35] Digital input DI27
Use the result of
digital input 29.
[37]
Digital input DI32
[37] Digital input DI32
Use the result of
digital input 32.
[38]
Digital input DI33
[38] Digital input DI33
Use the result of
digital input 33.
[39]
Start command
[39] Start command
A start command is
issued.
[40]
Drive stopped
[40] Drive stopped
A stop command
( Jog, Stop, Qstop, Coast) is issued –
and not from the SLC itself.
[41]
Reset Trip
[41] Reset Trip
A reset is issued
[42]
Auto-reset Trip
[42] Auto-reset Trip
An Auto reset is
performed.
[43]
Ok key
[43] OK key
The [OK] key is pressed.
[44]
Reset key
[44] Reset key
The [Reset] key is
pressed.
[45]
Left key
[45] Left key
The [
◄
] key is pressed.
[46]
Right key
[46] Right key
The [
►
] key is pressed.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
114