
3-92 Power Restore
Option: Function:
[0]
*
Off Resets the Digital Potentiometer reference to 0% after
power up.
[1]
On Restores the most recent Digital Potentiometer
reference at power up.
3-93 Maximum Limit
Range:
Function:
100 %
*
[-200 - 200
%]
Set the maximum permissible value for
the resultant reference. This is advisable if
the Digital Potentiometer is used for fine
tuning of the resulting reference.
3-94 Minimum Limit
Range:
Function:
-100 %
*
[-200 - 200
%]
Set the minimum permissible value for
the resultant reference. This is advisable
if the Digital Potentiometer is used for
fine tuning of the resulting reference.
3-95 Ramp Delay
Range:
Function:
Size
related
*
[ 0 -
0 ]
Enter the delay required from activation of
the digital potentiometer function until the
frequency converter starts to ramp the
reference. With a delay of 0 ms, the
reference starts to ramp as soon as
INCREASE/ DECREASE is activated. See also
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
65
3
3
Содержание VLT AutomationDrive FC 300 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT AutomationDrive...
Страница 210: ...www danfoss com drives MG33ME02 130R0334 MG33ME02 Rev 2012 02 20...
Страница 211: ......