[61]
Comparator 1
See parameter group 13-1*. If Comparator
1 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[62]
Comparator 2
See parameter group 13-1*. If Comparator
2 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[63]
Comparator 3
See parameter group 13-1*. If Comparator
3 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[64]
Comparator 4
See parameter group 13-1*. If Comparator
4 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[65]
Comparator 5
See parameter group 13-1*. If Comparator
5 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[70]
Logic Rule 0
See parameter group 13-4*. If Logic Rule
0 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[71]
Logic Rule 1
See parameter group 13-4*. If Logic Rule
1 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[72]
Logic Rule 2
See parameter group 13-4*. If Logic Rule
2 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[73]
Logic Rule 3
See parameter group 13-4*. If Logic Rule
3 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[74]
Logic Rule 4
See parameter group 13-4*. If Logic Rule
4 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[75]
Logic Rule 5
See parameter group 13-4*. If Logic Rule
5 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[80]
SL Digital
Output A
See
. The output
will go high whenever the Smart Logic
Action [38]
Set dig. out. A high
is
executed. The output will go low
whenever the Smart Logic Action [32] Set
dig. out. A low is executed.
[81]
SL Digital
Output B
See
. The input
will go high whenever the Smart Logic
Action
[39] Set dig. out. B high
is executed.
The input will go low whenever the
Smart Logic Action
[33] Set dig. out. B low
is executed.
[82]
SL Digital
Output C
See
. The input
will go high whenever the Smart Logic
Action
[40] Set dig. out. C high
is
executed. The input will go low whenever
the Smart Logic Action
[34] Set dig. out. C
low
is executed.
[83]
SL Digital
Output D
See
. The input
will go high whenever the Smart Logic
Action
[41] Set dig. out. D
high is
executed. The input will go low whenever
the Smart Logic Action
[35] Set dig. out. D
low
is executed.
[84]
SL Digital
Output E
See
. The input
will go high whenever the Smart Logic
Action
[42] Set dig. out. E high
is executed.
The input will go low whenever the
Smart Logic Action
[36] Set dig. out. E low
is executed.
[85]
SL Digital
Output F
See
. The input
will go high whenever the Smart Logic
Action
[43] Set dig. out. F high
is executed.
The input will go low whenever the
Smart Logic Action
[37] Set dig. out. F low
is executed.
[120] Local reference
active
Output is high when
=
[2] Local or when
= [0]
Linked to hand auto
at the same time as
the LCP is in [Hand On] mode.
Reference site
set in
Local
referenc
e
active
[120]
Remote
reference
active
[121]
Reference site:
Local
[2]
1
0
Reference site:
Remote
[1]
0
1
Reference site:
Linked to Hand/
Auto
Hand
1
0
Hand -> off
1
0
Auto -> off
0
0
Auto
0
1
Table 3.17
[121] Remote
reference
active
Output is high when
=
Remote
[1] or
Linked to hand/auto
[0]
while the LCP is in [Auto on] mode. See
above.
[122] No alarm
Output is high when no alarm is present.
[123] Start command
active
Output is high when there is an active
Start command (i.e. via digital input bus
connection or [Hand on] or [Auto on]),
and no Stop or Start command is active.
[124] Running
reverse
Output is high when the frequency
converter is running counter clockwise
(the logical product of the status bits
‘running’ AND ‘reverse’).
[125] Drive in hand
mode
Output is high when the frequency
converter is in [Hand on] mode (as
indicated by the LED light above [Hand
on]).
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
78
MG33ME02 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT AutomationDrive FC 300 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT AutomationDrive...
Страница 210: ...www danfoss com drives MG33ME02 130R0334 MG33ME02 Rev 2012 02 20...
Страница 211: ......