6-62 Terminal X30/8 Max. Scale
Range:
Function:
current signal output. Scale the output to
give a lower current than 20 mA at full
scale or 20 mA at an output below 100% of
the maximum signal value. If 20 mA is the
desired output current at a value between 0
- 100% of the ful-scale output, program the
percentage value in the parameter, i.e. 50%
= 20 mA. If a current between 4 and 20 mA
is desired at maximum output (100%),
calculate the percentage value as follows:
20
mA / desired maximum current x 100 %
i.e. 10 mA : 20 − 4
10 x 100 = 160 %
6-63 Terminal X30/8 Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00 %] Holds the level of Output X30/8 if
controlled by bus.
6-64 Terminal X30/8 Output Timeout Preset
Range:
Function:
0.00 %
*
[0.00 -
100.00 %]
Holds the preset level of Output X30/8.
In case of a bus timeout and a timeout
function is selected in
, the output will preset to
this level.
3.8.8 6-7* Analog Output 3 MCB 113
Parameters for configuring the scaling and limits for
analog output 3, Terminal X45/1 and X45/2. Analog
outputs are current outputs: 0/4–20 mA. Resolution on
analog output is 11 bit.
6-70 Terminal X45/1 Output
Option:
Function:
Select the function of Terminal X45/1 as an
analog current output.
[0]
No
operation
When no signal on the analog output.
[52]
MCO 305
0-20 mA
[53]
MCO 305
4-20 mA
[100] Output
frequency
0-20 mA
0 Hz = 0 mA; 100 Hz = 20 mA.
[101] Reference
0-20 mA
[Min - Max] 0% = 0
mA; 100% = 20 mA
[-Max - Max] -100% = 0
mA; 0% = 10 mA; +100% = 20 mA
[102] Feedback
6-70 Terminal X45/1 Output
Option:
Function:
[103] Motor
current 0-20
mA
Value is taken from
.
Inverter max. current (160% current) is equal
to 20 mA.
Example: Inverter norm current (11 kW) = 24
A. 160% = 38.4 A. Motor norm current = 22
A Read-out 11.46 mA.
20
mA x 22 A
38.4
A
= 11.46
mA
In case the norm motor current is equal to
20 mA, the output setting of
is:
IVLTMax x 100
IMotorNorm
= 38.4 x 100
22
= 175 %
[104] Torque rel
to lim 0-20
mA
The torque setting is related to setting in
[105] Torque rel
to rated
motor
torque 0-20
mA
The torque is related to the motor torque
setting.
[106] Power 0-20
mA
Taken from
[107] Speed 0-20
mA
Taken from
. 20 mA
= value in
[108] Torque ref.
0-20 mA
Torque reference related to 160% torque.
[109] Max Out
Freq 0-20
mA
In relation to
[130] Output freq.
4-20 mA
0 Hz = 4 mA, 100 Hz = 20 mA
[131] Reference
4-20 mA
[Min-Max] 0% = 4 mA;
100% = 20 mA
[-Max-Max] -100% = 4
mA; 0% = 12 mA; +100% = 20 mA
[132] Feedback
4-20 mA
[133] Motor cur.
4-20 mA
Value is taken from
.
Inverter max. current (160% current) is equal
to 20 mA.
Example: Inverter norm current (11 kW) = 24
A. 160% = 38.4 A. Motor norm current = 22
A Read-out 11.46 mA.
16
mA x 22 A
38.4
A
= 9.17
mA
In case the norm motor current is equal to
20 mA, the output setting of
is:
IVLTMax x 100
IMotorNorm
= 38.4 x 100
22
= 175 %
[134] Torque%
lim. 4-20
mA
The torque setting is related to setting in
.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
96