
6-50 Terminal 42 Output
Option:
Function:
[0]
*
No
operation
When no signal on the analog output.
[52]
MCO
0-20mA
[53]
MCO
4-20mA
[100] Output
frequency
0 Hz = 0 mA; 100 Hz = 20 mA.
[101] Reference
[Min - Max] 0% = 0 mA;
100% = 20 mA
[-Max - Max] -100% = 0
mA; 0% = 10 mA; +100% = 20 mA
[102] Feedback
[103] Motor
current
Value is taken from
Inverter max. current (160% current) is equal
to 20 mA.
Example: Inverter norm current (11 kW) = 24
A. 160% = 38.4 A. Motor norm current = 22A
Read-out 11.46 mA.
20
mA x 22 A
38.4
A
= 11.46
mA
In case the norm motor current is equal to 20
mA, the output setting of
is:
IVLTMax x 100
IMotorNorm
= 38.4 x 100
22
= 175 %
[104] Torque rel
to limit
The torque setting is related to setting in
[105] Torq relate
to rated
The torque is related to the motor torque
setting.
[106] Power
Taken from
.
[107] Speed
Taken from
. 20 mA =
value in
[108] Torque
Torque reference related to 160% torque.
[109] Max Out
Freq
0 Hz = 0 mA,
= 20
mA.
[113] PID
Clamped
Output
[119] Torque %
lim
[130] Output
freq.
4-20mA
0 Hz = 4 mA, 100 Hz = 20 mA
[131] Reference
4-20mA
[Min-Max] 0% = 4 mA;
100% = 20 mA
[-Max-Max] -100% = 4
mA; 0% = 12 mA; +100% = 20 mA
[132] Feedback
4-20mA
6-50 Terminal 42 Output
Option:
Function:
[133] Motor cur.
4-20mA
Value is taken from
.
Inverter max. current (160% current) is equal
to 20 mA.
Example: Inverter norm current (11 kW) = 24
A. 160% = 38.4 A. Motor norm current = 22 A
Read-out 11.46 mA.
16
mA x 22 A
38.4
A
+ 4
mA = 13.17 mA
In case the norm motor current is equal to 20
mA, the output setting of
is:
IVLTMax x 100
IMotorNorm
= 38.4 x 100
22
= 175 %
[134] Torq.% lim
4-20 mA
The torque setting is related to setting in
.
[135] Torq.%
nom 4-20
mA
The torque setting is related to the motor
torque setting.
[136] Power
4-20mA
Taken from
[137] Speed
4-20mA
Taken from
. 20 mA =
Value in
.
[138] Torque
4-20mA
Torque reference related to 160% torque.
[139] Bus ctrl.
0-20 mA
An output value set from fieldbus process
data. The output will work independently of
internal functions in the frequency converter.
[140] Bus ctrl.
4-20 mA
An output value set from fieldbus process
data. The output will work independently of
internal functions in the frequency converter.
[141] Bus ctrl
0-20mA t.o.
defines the
behaviour of the analog output in case of
bus time-out.
[142] Bus ctrl
4-20mA t.o.
defines the
behaviour of the analog output in case of
bus time-out.
[149] Torque %
lim 4-20mA
Analog output at zero torque = 12 mA.
Motoric torque will increase the output
current to max torque limit 20 mA (set in
).
Generative torque will decrease the output to
torque limit Generator Mode (set in
4-17 Torque Limit Generator Mode
)
Ex:
: 200% and
4-17 Torque Limit Generator Mode
: 200%. 20
mA = 200% Motoric and 4 mA = 200%
Generatoric.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
93
3
3
Содержание VLT AutomationDrive FC 300 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT AutomationDrive...
Страница 210: ...www danfoss com drives MG33ME02 130R0334 MG33ME02 Rev 2012 02 20...
Страница 211: ......