16-96 Maintenance Word
Range:
Function:
Positio
n 4
⇒
Valve
Fan
bea-
rings
Pump
bea-
rings
Motor
bea-
rings
Positio
n 3
⇒
Pump
seals
Tempe-
rature
transmi
tter
Flow
trans-
mitter
Pressur
e
transmi
tter
Positio
n 2
⇒
Drive
system
health
check
Drive
cooling
fan
Filter
Fan
belt
Positio
n 1
⇒
Warrant
y
0
hex
-
-
-
-
1
hex
-
-
-
+
2
hex
-
-
+
-
3
hex
-
-
+
+
4
hex
-
+
-
-
5
hex
-
+
-
+
6
hex
-
+
+
-
7
hex
-
+
+
+
8
hex
+
-
-
-
9
hex
+
-
-
+
A
hex
+
-
+
-
B
hex
+
-
+
+
C
hex
+
+
-
-
D
hex
+
+
-
+
E
hex
+
+
+
-
F
hex
+
+
+
+
Table 3.37
Example:
The Preventive Maintenance Word shows
040Ahex.
Position
1
2
3
4
hex-value
0
4
0
A
Table 3.38
The first digit 0 indicates that no items from
the fourth row requires maintenance
The second digit 4 refers to the third row
indicating that the Drive Cooling Fan requires
maintenance
The third digit 0 indicates that no items from
the second row requires maintenance
The fourth digit A refers to the top row
indicating that the Valve and the Pump
Bearings require maintenance
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
149