[101] Reference
[102] Feedback
[103] Motor current
[104] Torque relative to limit
[105] Torque relative to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out Freq
5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[0]
No operation
Select the desired display output for
terminal 27.
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out Freq
[119] Torque % lim
5-62 Pulse Output Max Freq #27
Range:
Function:
Size related
*
[0 - 32000
Hz]
Set the maximum frequency for
terminal 27, corresponding to the
output variable selected in
5-60 Terminal 27 Pulse Output
Variable
5-63 Terminal 29 Pulse Output Variable
Option:
Function:
[0]
*
No operation
Select the desired display output for
terminal 29. This parameter is
available for FC 302 only.
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
[108] Torque
5-63 Terminal 29 Pulse Output Variable
Option:
Function:
[109] Max Out Freq
[119] Torque % lim
5-65 Pulse Output Max Freq #29
Set the maximum frequency for terminal 29 corresponding to the
output variable set in
5-63 Terminal 29 Pulse Output Variable
.
Range:
Function:
5000 Hz
*
[0 - 32000 Hz]
5-66 Terminal X30/6 Pulse Output Variable
Select the variable for read-out on terminal X30/6.
This parameter is active when option module MCB 101 is
installed in the frequency converter.
Same options and functions as parameter group 5-6*.
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[119]
Torque % lim
NOTE
This parameter cannot be adjusted while the motor is
running.
5-68 Pulse Output Max Freq #X30/6
Select the maximum frequency on terminal X30/6 referring to
the output variable in
5-66 Terminal X30/6 Pulse Output Variable
.
This parameter is active when option module MCB 101 is
mounted in the frequency converter.
Range:
Function:
Size related
*
[0 - 32000 Hz]
3.7.7 5-7* 24 V Encoder Input
Connect the 24 V encoder to terminal 12 (24 V DC supply),
terminal 32 (Channel A), terminal 33 (Channel B), and
terminal 20 (GND). The digital inputs 32/33 are active for
encoder inputs when
[1] 24 V encoder
is selected in
1-02 Flux Motor Feedback Source
and
. The encoder used is a dual channel (A
and B) 24 V type. Max input frequency: 110 kHz.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
87