NOTE
When Auto Reset/Warning is selected the frequency
converter opens up for automatic restart.
Overview of functions, alarms and warnings
Function
No.
PTC
Relay
No Function
[0]
-
-
Safe Stop Alarm
[1]*
-
Safe Stop [A68]
Safe Stop Warning
[3]
-
Safe Stop [W68]
PTC 1 Alarm
[4]
PTC 1 Safe Stop
[A71]
-
PTC 1 Warning
[5]
PTC 1 Safe Stop
[W71]
-
PTC 1 & Relay A
[6]
PTC 1 Safe Stop
[A71]
Safe Stop [A68]
PTC 1 & Relay W
[7]
PTC 1 Safe Stop
[W71]
Safe Stop [W68]
PTC 1 & Relay A/W [8]
PTC 1 Safe Stop
[A71]
Safe Stop [W68]
PTC 1 & Relay W/A [9]
PTC 1 Safe Stop
[W71]
Safe Stop [A68]
Table 3.16
W means warning and A means alarm. For further information, see
Alarms and Warnings in section Troubleshooting in the Design Guide
or the Operating Instructions
A dangerous failure related to Safe Stop will give Alarm:
Dangerous Failure [A72].
Refer to in
5-20 Terminal X46/1 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1*
Digital Inputs
5-21 Terminal X46/3 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1*
Digital Inputs
5-22 Terminal X46/5 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1*
Digital Inputs
5-23 Terminal X46/7 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1*
Digital Inputs
5-24 Terminal X46/9 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1*
Digital Inputs
5-25 Terminal X46/11 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option
moduleMCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1*
Digital Inputs
5-26 Terminal X46/13 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 113 is installed in the frequency
converter. Functions are described under
parameter group 5-1*
Digital Inputs
3.7.3 5-3* Digital Outputs
The 2 solid-state digital outputs are common for terminals
27 and 29. Set the I/O function for terminal 27 in
, and set the I/O function for
terminal 29 in
.
NOTE
These parameters cannot be adjusted while the motor is
running.
[0]
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready
The control card is ready. E.g.: Feedback
from a frequency converter where the
control is supplied by an external 24 V
(MCB 107) and the main power to the
unit is not detected.
[2]
Drive ready
The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3]
Drive ready /
remote control
The frequency converter is ready for
operation and is in [Auto On] mode.
[4]
Enable / no
warning
Ready for operation. No start or stop
command is been given (start/disable).
No warnings are active.
[5]
VLT running
Motor is running and shaft torque
present.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
76
MG33ME02 - VLT
®
is a registered Danfoss trademark
3
3