Bit 0
Digital Output Terminal 27
Bit 1
Digital Output Terminal 29
Bit 2
Digital Output Terminal X 30/6
Bit 3
Digital Output Terminal X 30/7
Bit 4
Relay 1 output terminal
Bit 5
Relay 2 output terminal
Bit 6
Option B Relay 1 output terminal
Bit 7
Option B Relay 2 output terminal
Bit 8
Option B Relay 3 output terminal
Bit 9-15
Reserved for future terminals
Bit 16
Option C Relay 1 output terminal
Bit 17
Option C Relay 2 output terminal
Bit 18
Option C Relay 3 output terminal
Bit 19
Option C Relay 4 output terminal
Bit 20
Option C Relay 5 output terminal
Bit 21
Option C Relay 6 output terminal
Bit 22
Option C Relay 7 output terminal
Bit 23
Option C Relay 8 output terminal
Bit 24-31
Reserved for future terminals
Table 3.19
5-93 Pulse Out #27 Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00
%]
Set the output frequency transferred to
the output terminal 27 when the
terminal is configured as
[45] Bus
Controlled
in
.
5-94 Pulse Out #27 Timeout Preset
Range:
Function:
0.00 %
*
[0.00 -
100.00 %]
Set the output frequency transferred to
the output terminal 27 when the
terminal is configured as
[48] Bus Ctrl
Timeout
in
. And a time-out is detected.
5-95 Pulse Out #29 Bus Control
Range:
Function:
0.00 %
*
[0.00 -
100.00 %]
Set the output frequency transferred to
the output terminal 29 when the
terminal is configured as
[45] Bus
Controlled
in
.
This parameter only applies for FC 302.
5-96 Pulse Out #29 Timeout Preset
Range:
Function:
0.00 %
*
[0.00 -
100.00 %]
Set the output frequency transferred to
the output terminal 29 when the
terminal is configured as
[48] Bus Ctrl
Timeout
in
. And a time-out is detected.
This parameter only applies for FC 302.
5-97 Pulse Out #X30/6 Bus Control
Range:
Function:
0.00 %
*
[0.00 -
100.00 %]
Set the output frequency transferred to
the output terminal X30/6 when the
terminal is configured as 'Bus
Controlled' in
, Terminal X30/6 Pulse
Output Variable [45].
5-98 Pulse Out #X30/6 Timeout Preset
Range:
Function:
0.00 %
*
[0.00 -
100.00 %]
Set the output frequency transferred to
the output terminal X30/6 when the
terminal is configured as
[48] Bus Ctrl
Timeout
in
. And a time-out is
detected.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
89
3
3
Содержание VLT AutomationDrive FC 300 Series
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT AutomationDrive...
Страница 210: ...www danfoss com drives MG33ME02 130R0334 MG33ME02 Rev 2012 02 20...
Страница 211: ......