[6]
Running / no
warning
Output speed is higher than the speed
set in
1-81 Min Speed for Function at Stop
. The motor is running and there
are no warnings.
[7]
Run in range /
no warning
Motor is running within the programmed
current and speed ranges set in
to
. There are no warnings.
[8]
Run on
reference / no
warning
Motor runs at reference speed. No
warnings.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[11]
At torque limit
The torque limit set in
or
has been exceeded.
[12]
Out of current
range
The motor current is outside the range
set in
[13]
Below current,
low
Motor current is lower than set in
[14]
Above current,
high
Motor current is higher than set in
[15]
Out of range
Output frequency is outside the
frequency range set in
and
[16]
Below speed,
low
Output speed is lower than the setting in
.
[17]
Above speed,
high
Output speed is higher than the setting
in
[18]
Out of
feedback range
Feedback is outside the range set in
and
.
[19]
Below feedback
low
Feedback is below the limit set in
.
[20]
Above
feedback high
Feedback is above the limit set in
.
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[22]
Ready, no
thermal
warning
Frequency converter is ready for
operation and there is no over-
temperature warning.
[23]
Remote, ready,
no thermal
warning
Frequency converter is ready for
operation and is in [Auto On] mode.
There is no over-temperature warning.
[24]
Ready, no
over-/ under
voltage
Frequency converter is ready for
operation and the mains voltage is within
the specified voltage range (see
General
Specifications
section in the Design
Guide).
[25]
Reverse
Reversing. Logic ‘1’
when CW rotation of
the motor. Logic ‘0’ when CCW rotation
of the motor. If the motor is not rotating
the output will follow the reference.
[26]
Bus OK
Active communication (no time-out) via
the serial communication port.
[27]
Torque limit
and stop
Use in performing a coasting stop and in
torque limit condition. If the frequency
converter has received a stop signal and
is at the torque limit, the signal is Logic
‘0’.
[28]
Brake, no brake
warning
Brake is active and there are no warnings.
[29]
Brake ready, no
fault
Brake is ready for operation and there are
no faults.
[30]
Brake fault
(IGBT)
Output is Logic ‘1’ when the brake IGBT is
short-circuited. Use this function to
protect the frequency converter if there is
a fault on the brake modules. Use the
output/relay to cut out the main voltage
from the frequency converter.
[31]
Relay 123
Relay is activated when Control Word [0]
is selected in parameter group 8-**.
[32]
Mechanical
brake control
Enables control of an external mechanical
brake, see description in the section
Control of Mechanical Brake
, and
parameter group 2-2*
[33]
Safe stop
activated (FC
302 only)
Indicates that the safe stop on terminal
37 has been activated.
[40]
Out of ref
range
Active when the actual speed is outside
settings in
to
.
[41]
Below
reference low
Active when actual speed is below speed
reference setting.
[42]
Above
reference high
Active when actual speed is above speed
reference setting
[43]
Extended PID
Limit
[45]
Bus Ctrl
Controls output via bus. The state of the
output is set in
. The output state is retained in
the event of bus time-out.
[46]
Bus Ctrl On at
timeout
Controls output via bus. The state of the
output is set in
. In the event of bus time-out the
output state is set high (On).
[47]
Bus Ctrl Off at
timeout
Controls output via bus. The state of the
output is set in
. In the event of bus time-out the
output state is set low (Off).
[51]
MCO controlled Active when a MCO 302 or MCO 305 is
connected. The output is controlled from
option.
[55]
Pulse output
[60]
Comparator 0
See parameter group 13-1*. If Comparator
0 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark
77
3
3