3-40 Ramp 1 Type
Option:
Function:
A linear ramp will give constant acceleration
during ramping. An S-ramp will give non-
linear acceleration, compensating for jerk in
the application.
[0]
*
Linear
[1]
S-ramp
Const Jerk
Acceleration with lowest possible jerk.
[2]
S-ramp
Const Time
S-ramp based on the values set in
and
NOTE
If
[1] S-ramp Const Jerk
is selected and the reference during
ramping is changed the ramp time may be prolonged in
order to realize a jerk free movement which may result in
a longer start or stop time.
Additional adjustment of the S-ramp ratios or switching
initiators may be necessary.
3-41 Ramp 1 Ramp up Time
Range:
Function:
Size
related
*
[ 0.01 -
3600.00
s]
Enter the ramp-up time, i.e. the
acceleration time from 0 RPM to the
synchronous motor speed n
S
. Choose a
ramp-up time such that the output current
does not exceed the current limit in
during ramping. The
value 0.00 corresponds to 0.01 s in speed
mode. See ramp-down time in
.
Par. 3 − 41 =
tacc s x ns RPM
ref RPM
3-42 Ramp 1 Ramp Down Time
Range:
Function:
Size
related
*
[ 0.01 -
3600.00
s]
Enter the ramp-down time, that is, the
deceleration time from the synchronous
motor speed n
s
to 0 RPM. Choose a ramp-
down time such that no over-voltage arises
in the inverter due to regenerative
operation of the motor, and such that the
generated current does not exceed the
current limit set in
. The
value 0.00 corresponds to 0.01 s in speed
mode. See ramp-up time in
Par. 3 − 42 =
tdec s x ns RPM
ref RPM
3-45 Ramp 1 S-ramp Ratio at Accel. Start
Range:
Function:
50 %
*
[ 1 - 99.
%]
Enter the proportion of the total ramp-up
time (
) in which
3-45 Ramp 1 S-ramp Ratio at Accel. Start
Range:
Function:
the acceleration torque increases. The larger
the percentage value, the greater the jerk
compensation achieved, and thus the lower
the torque jerks occurring in the application.
3-46 Ramp 1 S-ramp Ratio at Accel. End
Range:
Function:
50 %
*
[ 1 - 99.
%]
Enter the proportion of the total ramp-up
time (
) in which
the acceleration torque decreases. The larger
the percentage value, the greater the jerk
compensation achieved, and thus the lower
the torque jerks in the application.
3-47 Ramp 1 S-ramp Ratio at Decel. Start
Range:
Function:
50 %
*
[ 1 - 99.
%]
Enter the proportion of the total ramp-down
time (
) where
the deceleration torque increases. The larger
the percentage value, the greater the jerk
compensation achieved, and thus the lower
the torque jerks in the application.
3-48 Ramp 1 S-ramp Ratio at Decel. End
Range:
Function:
50 %
*
[ 1 - 99.
%]
Enter the proportion of the total ramp-down
time (
) where
the deceleration torque decreases. The
larger the percentage value, the greater the
jerk compensation achieved, and thus the
lower the torque jerks in the application.
3.5.4 3-5* Ramp 2
Choosing ramp parameters, see parameter group 3-4*.
3-50 Ramp 2 Type
Option:
Function:
Select the ramp type, depending on
requirements for acceleration/deceleration. A
linear ramp will give constant acceleration
during ramping. An S-ramp will give non-
linear acceleration, compensating for jerk in
the application.
[0]
*
Linear
[1]
S-ramp
Const Jerk
Acceleration with lowest possible jerk
[2]
S-ramp
Const Time
S-ramp based on the values set in
and
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
60
MG33ME02 - VLT
®
is a registered Danfoss trademark
3
3