8-03 Control Timeout Time
Range:
Function:
Application
dependent*
[1.0 - 18000.0 s]
Enter the maximum time expected to pass between the reception of two consecutive telegrams. If
this time is exceeded, it indicates that the serial communication has stopped. The function selected
in par. 8-04
Control Timeout Function
Control Time-out Function
will then be carried out.
In LonWorks the following variables will trigger the Control Word Time parameter:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
8-04 Control Timeout Function
Option:
Function:
Select the time-out function. The time-out function is activated when the control word fails to be
updated within the time period specified in par. 8-03
Control Timeout Time
. Choice [20] only appears
after setting the N2 protocol.
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
[20]
N2 Override Release
In LonWorks, the time-out function is also activated when the following SNVT's fail to be updated within the time period specified in par. 8-03
Control
Timeout Time
:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
8-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid control word following a time-out. This parameter is active
only when par. 8-04
Control Timeout Function
is set to [Set-up 1-4].
[0]
Hold set-up
Retains the set-up selected in par. 8-04
Control Timeout Function
and displays a warning, until
par. 8-06
Reset Control Timeout
toggles. Then the frequency converter resumes its original set-up.
[1] *
Resume set-up
Resumes the set-up active prior to the time-out.