The Analog I/O option can be used for the control of devices such as actuators or valves, using the Extended Closed loop facility, thus removing control
from the existing control system. See section Parameters: Ext. Closed Loop – FC 322 parameter group 21-**. There are three independent closed loop
PID controllers.
26-00 Terminal X42/1 Mode
Option:
Function:
Terminal X42/1 can be programmed as an analog input accepting a voltage or input from either
Pt1000 (1000
വ
at 0
r
C) or Ni 1000 (1000
വ
at 0
r
C) temperature sensors. Select the desired mode.
Pt 1000
, [2] and
Ni 1000
[4] if operating in Celsius - Pt 1000 [3] and Ni 1000 [5] if operating in
Fahrenheit.
Notice: If the input is not in use, it must be set for Voltage!
If set for temperature and used as feed back, the unit must be set for either Celsius or Fahrenheit
(par. 20-12
Reference/Feedback Unit
, par. 21-10
Ext. 1 Ref./Feedback Unit
, par. 21-30
Ext. 2 Ref./
Feedback Unit
or par. 21-50
Ext. 3 Ref./Feedback Unit
).
[1] *
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-01 Terminal X42/3 Mode
Option:
Function:
Terminal X42/3 can be programmed as an analog input accepting a voltage or input from either Pt
1000 or Ni 1000 temperature sensors. Select the desired mode.
Pt 1000, [2] and Ni 1000, [4] if operating in Celsius - Pt 1000, [3] and Ni 1000, [5] if operating in
Fahrenheit.
Notice: If the input is not in use, it must be set for Voltage!
If set for temperature and used as feed back, the unit must be set for either Celsius or Fahrenheit
(par. 20-12
Reference/Feedback Unit
, par. 21-10
Ext. 1 Ref./Feedback Unit
, par. 21-30
Ext. 2 Ref./
Feedback Unit
or par. 21-50
Ext. 3 Ref./Feedback Unit
).
[1] *
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
255
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx