13-41 Logic Rule Operator 1
Array [6]
Option:
Function:
Select the first logical operator to use on the Boolean inputs from par. 13-40
Logic Rule Boolean 1
and par. 13-42
Logic Rule Boolean 2
.
[13 -XX] signifies the boolean input of par. 13-*.
[0] *
DISABLED
Ignores par. , par. 13-43
Logic Rule Operator 2
, and par. 13-44
Logic Rule Boolean 3
.
[1]
AND
Evaluates the expression [13-40] AND [13-42].
[2]
OR
evaluates the expression [13-40] OR[13-42].
[3]
AND NOT
evaluates the expression [13-40] AND NOT [13-42].
[4]
OR NOT
evaluates the expression [13-40] OR NOT [13-42].
[5]
NOT AND
evaluates the expression NOT [13-40] AND [13-42].
[6]
NOT OR
evaluates the expression NOT [13-40] OR [13-42].
[7]
NOT AND NOT
evaluates the expression NOT [13-40] AND NOT [13-42].
[8]
NOT OR NOT
evaluates the expression NOT [13-40] OR NOT [13-42].
13-42 Logic Rule Boolean 2
Array [6]
Option:
Function:
Select the second boolean (TRUE or FALSE) input for the selected logic rule.
See par. 13-40
Logic Rule Boolean 1
for further descriptions of choices and their functions.
[0] *
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
149
2