15-07 Reset Running Hours Counter
Option:
Function:
[0] *
Do not reset
Select
Do not reset
[0] if no reset of the Running Hours counter is desired.
[1]
Reset counter
Select
Reset counter
[1] and press [OK] to reset the Running Hours counter (par. 15-01
Running
Hours
) and par. 15-08
Number of Starts
to zero (see also par. 15-01
Running Hours
).
15-08 Number of Starts
Range:
Function:
0*
[0 - 2147483647 ]
This is a read out parameter only. The counter shows the numbers of starts and stops caused by a
normal Start/Stop command and/or when entering/leaving sleep mode.
NB!
This parameter will be reset when resetting par. 15-07
Reset Running Hours Counter
.
2.14.3 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data sources (par. 15-10
Logging Source
) at individual rates (par. 15-11
Logging Interval
). A trigger
event (par. 15-12
Trigger Event
) and window (par. 15-14
Samples Before Trigger
) are used to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
Select which variables are to be logged.
None
[1600]
Control Word
[1601]
Reference [Unit]
[1602]
Reference %
[1603]
Status Word
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor Voltage
[1613]
Frequency
[1614]
Motor Current
[1616]
Torque [Nm]
[1617]
Speed [RPM]
[1618]
Thermal Motor Load
[1622]
Torque [%]
[1630]
DC Link Voltage
[1632]
Brake Energy / s
[1633]
Brake Energy / 2 min
[1634]
Heatsink Temp.
[1635]
Thermal Drive Load
[1650]
External Reference
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
167
2