26-43 Terminal X42/7 Bus Control
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the level of terminal X42/7 if controlled by bus.
26-44 Terminal X42/7 Timeout Preset
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the preset level of terminal X42/7.
In case of a bus timeout and a timeout function is selected in par. 26-50
Terminal X42/9 Output
the
output will preset to this level.
26-50 Terminal X42/9 Output
Option:
Function:
Set the function of terminal X42/9.
[0] *
No operation
[100]
Output freq. 0-100
: 0 - 100 Hz, (0-20 mA)
[101]
Reference Min-Max
: Minimum reference - Maximum reference, (0-20 mA)
[102]
Fe-200%
: -200% to +200% of par. 20-14
Maximum Reference/Feedb.
, (0-20 mA)
[103]
Motor cur. 0-Imax
: 0 - Inverter Max. Current (par. 16-37
Inv. Max. Current
), (0-20 mA)
[104]
Torque 0-Tlim
: 0 - Torque limit (par. 4-16
Torque Limit Motor Mode
), (0-20 mA)
[105]
Torque 0-Tnom
: 0 - Motor rated torque, (0-20 mA)
[106]
Power 0-Pnom
: 0 - Motor rated power, (0-20 mA)
[107]
Speed 0-HighLim
: 0 - Speed High Limit (par. 4-13
Motor Speed High Limit [RPM]
and par. 4-14
Motor Speed High
Limit [Hz]
), (0-20 mA)
[108]
-160%
[109]
Out frq 0-Fmax
[113]
Ext. Closed Loop 1
: 0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2
: 0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3
: 0 - 100%, (0-20 mA)
[139]
Bus ctrl.
: 0 - 100%, (0-20 mA)
[141]
Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
26-51 Terminal X42/9 Min. Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scale the minimum output of the selected analog signal at terminal X42/9, as a percentage of the
maximum signal level. E.g. if a 0 V is desired at 25% of the maximum output value. Then programme
25%. Scaling values up to 100% can never be higher than the corresponding setting in
par. 26-52
Terminal X42/9 Max. Scale
.
See principle graph for par. 6-51
Terminal 42 Output Min Scale
.