2.6.3 4-5* Adj. Warnings
Define adjustable warning limits for current, speed, reference and feedback.
NB!
Not visible in display, only in VLT Motion Control Tool, MCT 10.
Warnings are shown on display, programmed output or serial bus.
4-50 Warning Current Low
Range:
Function:
0.00 A*
[Application dependant]
Enter the I
LOW
value. When the motor current falls below this limit (I
LOW
), the display reads CURRENT
LOW. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02. Refer to the drawing in this section.
4-51 Warning Current High
Range:
Function:
Application
dependent*
[Application dependant]
4-52 Warning Speed Low
Range:
Function:
0 RPM*
[Application dependant]
Enter the n
LOW
value. When the motor speed falls below this limit (n
LOW
) the display reads SPEED
LOW. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02. Programme the lower signal limit of the motor speed, n
LOW
, within the
normal working range of the frequency converter. Refer to the drawing in this section.
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
67