6-47 Term. X30/12 Live Zero
Option:
Function:
This parameter makes it possible to disable the Live Zero monitoring. E.g. to be used if the analog
outputs are used as part of a decentral I/O system (e.g. when not part of any frequency converter
related control functions, but feeding an external control system with data)
[0] *
Disabled
[1]
Enabled
2.8.7 6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog output 1, i.e. Terminal 42. Analog outputs are current outputs: 0/4 – 20 mA. Common terminal
(terminal 39) is the same terminal and has the same electrical potential for analog common and digital common connection. Resolution on analog output
is 12 bit.
6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42 as an analog current output. A motor current of 20 mA corre-
sponds to I
max
.
[0] *
No operation
[100] *
Output freq. 0-100
: 0 - 100 Hz, (0-20 mA)
[101]
Reference Min-Max
: Minimum reference - Maximum reference, (0-20 mA)
[102]
Fe-200%
: -200% to +200% of par. 20-14, (0-20 mA)
[103]
Motor cur. 0-Imax
: 0 - Inverter Max. Current (par. 16-37), (0-20 mA)
[104]
Torque 0-Tlim
: 0 - Torque limit (par. 4-16), (0-20 mA)
[105]
Torque 0-Tnom
: 0 - Motor rated torque, (0-20 mA)
[106]
Power 0-Pnom
: 0 - Motor rated power, (0-20 mA)
[107]
Speed 0-HighLim
: 0 - Speed High Limit (par. 4-13 and par. 4-14), (0-20 mA)
[108]
-160%
: (0-20 mA)
[109]
Out frq 0-Fmax
:
[113]
Ext. Closed Loop 1
: 0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2
: 0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3
: 0 - 100%, (0-20 mA)
[116]
Cascade Reference
[130]
Out frq 0-100 4-20mA
: 0 - 100 Hz
[131]
Reference 4-20mA
: Minimum Reference - Maximum Reference
[132]
Feedback 4-20mA
: -200% to +200% of par. 20-14
[133]
Motor cur. 4-20mA
: 0 - Inverter Max. Current (par. 16-37
Inv. Max. Current
)
[134]
Torq.0-lim 4-20 mA
: 0 - Torque limit (par. 4-16)
[135]
Torq.0-nom 4-20 mA
: 0 - Motor rated torque
[136]
Power 4-20mA
: 0 - Motor rated power
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p