0-76 DST/Summertime Start
Range:
Function:
Application
dependent*
[Application dependant]
0-77 DST/Summertime End
Range:
Function:
Application
dependent*
[Application dependant]
0-79 Clock Fault
Option:
Function:
Enables or disables the clock warning, when the clock has not been set or has been reset due to a
power-down and no backup is installed.
[0] *
Disabled
[1]
Enabled
0-81 Working Days
Array with 7 elements [0] - [6] displayed below parameter number in display. Press OK and step between elements by means of
Ⴃ
and
Ⴍ
buttons on
the LCP.
Option:
Function:
Set for each weekday if it is a working day or a non-working day. First element of the array is
Monday. The working days are used for Timed Actions.
[0] *
No
[1]
Yes
0-82 Additional Working Days
Array with 5 elements [0] - [4] displayed below parameter number in display. Press OK and step between elements by means of
Ⴃ
and
Ⴍ
buttons on
the LCP.
Range:
Function:
Application
dependent*
[Application dependant]
0-83 Additional Non-Working Days
Array with 15 elements [0] - [14] displayed below parameter number in display. Press OK and step between elements by means of
Ⴃ
and
Ⴍ
buttons
on the LCP.
Range:
Function:
Application
dependent*
[Application dependant]
0-89 Date and Time Readout
Range:
Function:
0*
[0 - 0 ]
Displays the current date and time. The date and time is updated continuously.
The clock will not begin counting until a setting different from default has been made in
par. 0-70
Date and Time
.